Single-container, drop-on-any-Linux-host bundle that does two things at once: replaces Dell PowerEdge stock fan curves with a per-class adaptive PID, and ships a full per-host Prometheus exporter stack (node_exporter, cadvisor, ipmi_exporter, smartctl_exporter, nvidia_gpu_exporter, vmagent) in the same image. Each sub-service probes its hardware on start and self-disables if absent, so the same image runs on a Dell R730xd with a Tesla GPU, an Unraid box on consumer hardware, and a plain Debian VM with nothing exotic attached. Set two env vars (image, Prometheus URL) and it runs.
┌──────────────────────── your host ────────────────────────┐
│ │
│ host-agent (single container, s6-supervised) │
│ ├─ fan-controller (Dell IPMI PID controller) │
│ ├─ node_exporter :9100 │
│ ├─ cadvisor :8089 │
│ ├─ ipmi_exporter :9290 │
│ ├─ smartctl_exporter:9633 │
│ ├─ nvidia_gpu_expo. :9835 │
│ └─ vmagent ──────────── remote_write ──┐ │
│ │ │
└──────────────────────────────────────────┼────────────────┘
│
┌────────────▼────────────┐
│ your Prometheus │
│ (or VictoriaMetrics, │
│ Grafana Cloud, Mimir) │
└─────────────────────────┘
At a glance
| Image | ghcr.io/mattjackson/host-agent:latest (linux/amd64) |
| Chassis profiles shipped | 13 (4 tested on real hardware, 9 conservative defaults) |
| External Go dependencies | zero (stdlib only, no go.sum, vendor-free build) |
- Quick start
- What's inside
- Install
- Configuration
- Dashboard
- Fan controller
- Per-chassis profiles
- Tested hardware
- FAQ
- Comparison vs alternatives
- Architecture rationale
- Operational
- Development
- Contributing
- Security
- Changelog
- License
On Unraid? Skip this block and go straight to Option C — the install path is different (and simpler) because the URL lives in appdata, not env.
# 1. Pick where you're pushing metrics.
export HOST_AGENT_IMAGE=ghcr.io/mattjackson/host-agent:latest
export PROMETHEUS_REMOTE_WRITE_URL=https://your.prometheus/api/v1/write
# 2. (Dell hosts only) load the IPMI kernel module + create state dir.
sudo modprobe ipmi_devintf
echo ipmi_devintf | sudo tee /etc/modules-load.d/ipmi.conf
sudo install -d -m 755 /var/lib/host-agent/state
# 3. Run.
docker run -d \
--name host-agent \
--restart unless-stopped \
--privileged \
--network host \
--cgroupns host \
-e PROMETHEUS_REMOTE_WRITE_URL \
-v /:/host:ro,rslave \
-v /sys:/sys:ro \
-v /run/docker.sock:/run/docker.sock \
-v /run/containerd:/run/containerd:ro \
-v /var/lib/docker:/var/lib/docker:ro \
-v /dev:/dev \
-v /var/lib/host-agent:/var/lib/host-agent \
"$HOST_AGENT_IMAGE"The container appears in your Prometheus on its first scrape, labeled with host=<kernel-hostname>. There's no central config to edit when you add a new box — the agent introduces itself.
| sub-service | port | runs when | otherwise |
|---|---|---|---|
fan-controller |
— | /dev/ipmi0 exists AND BMC is Dell |
sleep |
node_exporter |
9100 | always | always |
cadvisor |
8089 | /run/docker.sock mounted |
sleep |
ipmi_exporter |
9290 | /dev/ipmi0 exists |
sleep |
smartctl_exporter |
9633 | always (auto-discovers) | always |
nvidia_gpu_exporter |
9835 | nvidia-smi is present |
sleep |
unraid-disks |
— | /host/etc/unraid-version exists |
sleep |
apt-status |
— | host has /usr/lib/update-notifier/apt-check (Debian/Ubuntu) |
sleep |
vmagent |
8429 | PROMETHEUS_REMOTE_WRITE_URL set |
sleep |
unraid-disks emits a textfile metric unraid_disk_info{device,slot} mapping Unraid's array slot labels (disk1, parity, cache, ...) to Linux device names by parsing /var/local/emhttp/disks.ini. Dashboards join on (host, device) to display the slot label instead of the bare sdX letter — matches the bay labeling in Unraid's own UI.
apt-status runs chroot /host /usr/lib/update-notifier/apt-check once an hour and emits host_apt_updates_pending{type="all"|"security"} plus host_reboot_required (0/1, gated on /var/run/reboot-required). Useful when you've disabled unattended-upgrades on production hosts and want a "pending updates" panel as your planned-patch-cycle to-do list; the reboot-required flag is the single best post-upgrade safety check.
node_exporter reads fan-controller runtime textfiles from /run/host-agent/state, so setpoints, temperatures, and adaptive targets appear alongside standard node metrics on :9100. The image mounts /run/host-agent as a 256 MB tmpfs before s6 starts; this keeps the textfiles and vmagent's unsent queue in RAM even with older Docker templates. Its filesystem collector excludes /boot and removable USB mounts while retaining normal capacity metrics for other filesystems.
Adaptive controller (v0.2.0+). The fan controller has two layers. A fast PID layer cycles every 15s and emits per-class fan-speed candidates; max() across all candidates plus per-class proximity floors drives the chassis. A slow intent layer (HOST_AGENT_MODE=max-cool|balanced|min-noise|eco) sits above it and drifts per-class targets every 10 min toward the chassis's actual equilibrium — within hardware envelopes encoded in the agent (CPU TJunction, NVIDIA passive datacenter envelope, Google HDD optimal band, NAND specs). Operators state intent; the agent picks numbers. Per-class env-var overrides (CPU_TARGET=70 etc.) still win and disable adaptive on that class. See docs/adaptive-controller-v2.md for the full design.
See Quick start. Idempotent re-runs of the same docker run aren't (Docker errors on the name conflict); use docker rm -f host-agent then re-run, or use install/install.sh which does that automatically.
# docker-compose.yml
services:
host-agent:
image: ${HOST_AGENT_IMAGE:?HOST_AGENT_IMAGE must be set}
container_name: host-agent
restart: unless-stopped
privileged: true
network_mode: host
cgroup: host
runtime: ${HOST_AGENT_RUNTIME:-runc}
environment:
- NVIDIA_VISIBLE_DEVICES=all
- NVIDIA_DRIVER_CAPABILITIES=utility
- PROMETHEUS_REMOTE_WRITE_URL=${PROMETHEUS_REMOTE_WRITE_URL:?must be set}
- PROMETHEUS_REMOTE_WRITE_BEARER_TOKEN=${PROMETHEUS_REMOTE_WRITE_BEARER_TOKEN:-}
- PROMETHEUS_REMOTE_WRITE_USERNAME=${PROMETHEUS_REMOTE_WRITE_USERNAME:-}
- PROMETHEUS_REMOTE_WRITE_PASSWORD=${PROMETHEUS_REMOTE_WRITE_PASSWORD:-}
- PROMETHEUS_REMOTE_WRITE_TLS_INSECURE_SKIP_VERIFY=${PROMETHEUS_REMOTE_WRITE_TLS_INSECURE_SKIP_VERIFY:-}
volumes:
- /:/host:ro,rslave
- /sys:/sys:ro
- /run/docker.sock:/run/docker.sock
- /run/containerd:/run/containerd:ro
- /var/lib/docker:/var/lib/docker:ro
- /dev:/dev
- /var/lib/host-agent:/var/lib/host-agentDrop the two env vars in an .env next to the compose, then docker compose up -d. The infra/deploy.sh wrapper in this repo handles the auto-detect-nvidia-runtime case.
The install/host-agent.xml template is consumable directly from GitHub — no Community Applications submission needed. Set the Prometheus endpoint in the template's PROMETHEUS_REMOTE_WRITE_URL field.
One-time SSH setup (fetches the template):
curl -sfLO --output-dir /boot/config/plugins/dockerMan/templates-user \
https://raw.githubusercontent.com/MattJackson/host-agent/main/install/host-agent.xmlOn a Dell PowerEdge running Unraid, load the host kernel's IPMI interface at
each boot so /dev/ipmi0 is available before Docker starts. Add this block
once to /boot/config/go (preserve the rest of that file):
/sbin/modprobe ipmi_si
/sbin/modprobe ipmi_devintfThe container includes the IPMI userspace tools and talks through the host's
/dev/ipmi0; it cannot provide the host kernel driver itself. The template
bind-mounts /mnt/user/appdata/host-agent for learned state and gives the
container a RAM-backed /run for metrics, temporary files, and vmagent's
unsent queue. Node-exporter excludes /boot and removable USB filesystems;
cAdvisor disk and filesystem metrics are disabled. Filesystem capacity remains
available for non-removable filesystems. SMART discovery excludes the block
device backing /boot. A restart can lose unsent remote-write samples and the
observer's short rolling window.
Then in the web UI: Docker tab → Add Container → Template dropdown → pick host-agent under "User templates" → Apply.
Set the Prometheus /api/v1/write URL in the template. If your receiver needs auth, toggle Advanced View to expose the optional bearer-token / basic-auth / TLS-skip fields.
All paths and the --cgroupns=host flag are pre-baked into the template. To get listed in Community Applications search, submit the XML to Squidly271/AppFeed — not required for personal use.
Future updates — just click Force Update in the Docker tab. If a release adds new template fields (rare), the release notes will tell you to re-run the curl above; otherwise leave the template alone.
export HOST_AGENT_IMAGE=ghcr.io/mattjackson/host-agent:latest
export PROMETHEUS_REMOTE_WRITE_URL=https://your.prometheus/api/v1/write
curl -sf https://raw.githubusercontent.com/MattJackson/host-agent/main/install/install.sh | shIdempotent (stops + removes any existing host-agent container first). All flags hardcoded — to change them, fork or build a new image, don't edit the script per host.
End-to-end walkthrough for a freshly installed Ubuntu (or Debian) server with nothing on it yet. Goes from apt update to host-agent reporting in your Prometheus. Tested on Ubuntu 24.04 LTS server, fresh install.
# 1. Set the hostname FIRST — host-agent stamps every metric series with
# `host=$(hostname -s)`, so this determines how the box appears in
# Prometheus and Grafana. Skipping this step gives you a series labeled
# "ubuntu" (or, on some setups, with no host label at all).
sudo hostnamectl set-hostname <your-host>
# 2. Ubuntu prerequisites
sudo apt update && sudo apt install -y ca-certificates curl gnupg lsb-release
# 3. Docker engine (official repo, not the snap)
sudo install -m 0755 -d /etc/apt/keyrings
curl -fsSL https://download.docker.com/linux/ubuntu/gpg | \
sudo gpg --dearmor -o /etc/apt/keyrings/docker.gpg
sudo chmod a+r /etc/apt/keyrings/docker.gpg
echo "deb [arch=$(dpkg --print-architecture) signed-by=/etc/apt/keyrings/docker.gpg] \
https://download.docker.com/linux/ubuntu $(lsb_release -cs) stable" | \
sudo tee /etc/apt/sources.list.d/docker.list
sudo apt update && sudo apt install -y docker-ce docker-ce-cli containerd.io \
docker-buildx-plugin docker-compose-plugin
sudo usermod -aG docker $USER && newgrp docker
# 4. (Dell hosts only) load the IPMI kernel module so the fan controller
# can talk to the BMC. Harmless skip on non-Dell hardware.
sudo modprobe ipmi_devintf
echo ipmi_devintf | sudo tee /etc/modules-load.d/ipmi.conf
# 5. State dir (persists fan-controller learnings + vmagent WAL)
sudo install -d -m 755 /var/lib/host-agent/state
# 6. host-agent — adjust PROMETHEUS_REMOTE_WRITE_URL to your receiver
sudo docker run -d \
--name host-agent \
--restart unless-stopped \
--privileged \
--network host \
--cgroupns host \
-e PROMETHEUS_REMOTE_WRITE_URL=https://your.prometheus/api/v1/write \
-l com.centurylinklabs.watchtower.enable=true \
-v /:/host:ro,rslave \
-v /sys:/sys:ro \
-v /run/docker.sock:/run/docker.sock \
-v /run/containerd:/run/containerd:ro \
-v /var/lib/docker:/var/lib/docker:ro \
-v /dev:/dev \
-v /var/lib/host-agent:/var/lib/host-agent \
ghcr.io/mattjackson/host-agent:latest
# 7. Watchtower — auto-pulls host-agent updates from ghcr.io (label-gated,
# only touches containers with watchtower.enable=true, which host-agent
# sets in step 6).
sudo docker run -d --name watchtower --restart unless-stopped \
-v /var/run/docker.sock:/var/run/docker.sock \
containrrr/watchtower --label-enable --interval 300Within ~1 minute, the box appears in your Prometheus tagged host=<your-host>. From then on, every host-agent release lands automatically (Watchtower's 5-min poll on :latest).
Watch-outs:
- Hostname set late. If you set hostname after starting the container, restart it (
docker restart host-agent) so vmagent re-readshostname -sfor its external label.- All 4 docker mounts are required. Skipping any of
/,/run/docker.sock,/run/containerd, or/var/lib/dockersilently breaks cadvisor (no container metrics) and gives node-exporter the container's/procview instead of the host's. The minimal-v /sys:/sys:ro -v /dev:/devset is not sufficient — it starts, it pushes, but half your panels are empty.- Auth. If your Prometheus needs auth, add
-e PROMETHEUS_REMOTE_WRITE_BEARER_TOKEN=...(or the basic-auth pair). See Configuration.
Every knob is an env var. Required:
| var | what it is |
|---|---|
HOST_AGENT_IMAGE |
image to pull, e.g. ghcr.io/mattjackson/host-agent:latest |
PROMETHEUS_REMOTE_WRITE_URL |
your receiver's /api/v1/write endpoint |
Pass the receiver URL through the container environment. Host-agent does not read a persistent URL file at runtime.
Optional — Prometheus push auth (bearer XOR basic):
| var | default | what |
|---|---|---|
PROMETHEUS_REMOTE_WRITE_BEARER_TOKEN |
— | sent as Authorization: Bearer … |
PROMETHEUS_REMOTE_WRITE_USERNAME / _PASSWORD |
— | HTTP basic auth |
PROMETHEUS_REMOTE_WRITE_TLS_INSECURE_SKIP_VERIFY |
false |
self-signed certs |
Optional — GPU runtime:
| var | default | what |
|---|---|---|
HOST_AGENT_RUNTIME |
runc |
set to nvidia to inject nvidia-smi via NVIDIA Container Runtime |
Optional — adaptive controller intent (v0.2.0+):
| var | default | what |
|---|---|---|
HOST_AGENT_MODE |
unset (v1 fixed targets) | one of max-cool, balanced, min-noise, eco. Replaces per-class fixed targets with envelope-derived initials, then drifts them every 10 min toward observed equilibrium. |
HOST_AGENT_ADAPTIVE_DISABLED |
false |
kill-switch — keeps the observer off entirely. Falls back to pure v1 fixed-target behavior. |
ADAPTIVE_CYCLE_MINUTES |
10 |
reconcile cadence |
OBSERVER_WINDOW_MINUTES |
120 |
rolling sample window per class |
Optional — per-class fan controller overrides (advanced; override the chassis profile AND disable adaptive on that class):
| var | default (from profiles/default.env) |
what |
|---|---|---|
CPU_TARGET / CPU_EMERGENCY / CPU_DEADBAND / CPU_APPROACH_WINDOW |
70 / 80 / 3 / 10 |
CPU class PID |
GPU_TARGET / GPU_EMERGENCY / GPU_DEADBAND / GPU_APPROACH_WINDOW |
83 / 90 / 2 / 7 |
passive GPU PID |
ACTIVE_GPU_OWN_FAN_THRESHOLD / ACTIVE_GPU_EMERGENCY |
85 / 88 |
active GPU (own-fan-driven) assist threshold + temp safety net |
HDD_TARGET / HDD_EMERGENCY / HDD_DEADBAND / HDD_APPROACH_WINDOW |
40 / 50 / 3 / 5 |
HDD PID |
SSD_TARGET / SSD_EMERGENCY / SSD_DEADBAND / SSD_APPROACH_WINDOW |
50 / 65 / 5 / 8 |
SSD PID |
PROFILE |
autodetected | force a profile slug (e.g. r730xd); overrides dmidecode |
See profiles/default.env for the full reference + tuning notes.
The receiver needs Prometheus 2.33+ with --web.enable-remote-write-receiver, or any compatible TSDB:
- Prometheus
- VictoriaMetrics (single-node or cluster)
- Grafana Mimir
- Cortex
- Grafana Cloud (hosted)
A minimal local setup lives in examples/server-side/ — a tiny Prometheus + Grafana compose that takes a fresh user end-to-end in ~5 min. The bundled Prometheus runs with --web.enable-remote-write-receiver and --enable-feature=promql-experimental-functions (the dashboard uses sort_by_label for natural Unraid drive ordering).
A pre-built Grafana dashboard for host-agent data lives at examples/server-side/grafana/dashboards/server-overview.json (auto-provisioned by the bundled server-side compose; or import via Grafana → Dashboards → New → Import → paste JSON). Sections:
- Temperatures — CPU per-socket, IPMI inlet/exhaust, GPU die, per-drive SMART
- Fan setpoint + RPM — controller's commanded % vs measured RPM per fan
- CPU / RAM / disk / network — standard
node_exporterpanels - GPU util / mem / power — from
nvidia_gpu_exporter - Drives — per-drive temperature timeseries with Unraid slot labels where applicable
- Build panel — which container build + chassis profile each host reports
The dashboard is hardware-agnostic (uses class=~"cpu1|cpu2" and device=~".+" patterns) so it adapts to whatever each host actually exposes. An Adaptive Controller dashboard row (per-class targets vs envelope, drift events, fit score per mode) lights up when HOST_AGENT_MODE is set.
read CPU temps (coretemp via /sys, IPMI entity 3.x fallback)
read GPU temps (nvidia-smi), classify passive vs active
read HDD/SSD (smartctl --scan, then -A -n standby per drive)
├─ HDD: classified by rotation_rate > 0
└─ SSD/NVMe: rotation_rate = 0
Re-assert manual fan mode every cycle: iDRAC's third-party PCIe cooling
response silently flips the BMC back to auto (→ 100% fans)
within ~30s when a non-Dell GPU/HBA is present. Idempotent
IPMI call; ~10ms per cycle.
Emergency override: any class >= its class_EMERGENCY ⇒ fans = 100%, stay
until ALL classes drop below {emergency - hysteresis}.
Per-class PID candidates (CPU, passive_GPU, HDD, SSD):
candidate = clamp(current_speed + P*err + D*d_temp,
MIN_FAN, MAX_FAN)
# Asymmetric deadband: positive errors always step up, even inside
# the deadband. Negative errors inside deadband drift toward MIN_FAN
# by DEADBAND_DRIFT_RATE per cycle.
Saturation escape (v0.3.7+): when above target AND already at MAX_FAN
AND temp is not rising, drift candidate DOWN by
DEADBAND_DRIFT_RATE to probe whether less fan also
holds equilibrium. Self-correcting — if load really is
near max cooling capacity, next cycle's P+D pushes
back up. Pairs with adaptive's saturation penalty so
target rises to the achievable equilibrium and error
closes.
Per-class proximity floor (linear ramp from approach_window edge to emergency):
pf[class] = ramp(class_temp,
EMERGENCY - APPROACH_WINDOW, EMERGENCY,
MIN_FAN, MAX_FAN)
# State-free — catches fast spikes the PID step can't react to.
Active-GPU assist (own-fan cards like RTX A5500 — chassis can't cool the
die, only the inlet air; signal is the card's OWN fan saturation, not
die temp):
if own_fan >= ACTIVE_GPU_OWN_FAN_THRESHOLD:
assist = ramp(own_fan,
ACTIVE_GPU_OWN_FAN_THRESHOLD, 100,
MIN_FAN, MAX_FAN)
final_speed = max(cpu_cand, pg_cand, hdd_cand, ssd_cand,
cpu_pf, pg_pf, hdd_pf, ssd_pf,
ag_assist)
SetFan(final_speed) # unconditional every cycle, not on change —
# BMC's revert-watchdog tracks the SetFan command.
EWMA baseline (checkpointed to /var/lib/host-agent/state/base every six hours and on graceful shutdown):
base_speed = (1 - α) * base_speed + α * current_speed
# α = 0.001/cycle → settles over 24-48 hrs of operation.
The whole loop runs every INTERVAL_SEC=15s. Temperature metrics are rendered to RAM-backed /run/host-agent/state; learned state is checkpointed at most every six hours and on graceful shutdown. Observer samples stay in RAM and warm up again after restart. All temperature thresholds, gains, and timing constants come from the chassis profile + class defaults — no hardcoded fan values, no lookup tables, no piecewise rules.
Adaptive intent layer (slow loop, every ADAPTIVE_CYCLE_MINUTES=10). With HOST_AGENT_MODE set, an observer accumulates per-class (temperature, fan-demand, inlet) samples in a 20-minute rolling window in RAM. Each reconcile cycle scores projected targets using the mode's score function and bounded class envelopes. Adaptive target state is checkpointed to /var/lib/host-agent/state/adaptive.json every six hours and on graceful shutdown; raw samples warm up again after restart. See docs/adaptive-controller-v2.md for the full design.
profiles/<model>.env files are autoloaded by dmidecode product_name. Currently shipped:
| chassis | MIN_FAN | tested | notes |
|---|---|---|---|
r730xd |
10 | yes | BMC clamps PWM <10 to a safety RPM (5040). No fan-stall risk. |
r730 |
10 | yes | Same firmware family as R730xd. |
r410 |
20 | yes | BMC obeys low PWM literally — going lower stalls fans. |
dell_xc730xd_12 |
10 | yes | Dell XC = Nutanix OEM rebadge of R730xd. Same BMC. |
r310 / r510 / r610 / r710 / r720 / r720xd |
20 | no | Conservative — older BMC firmware behavior not probed. |
r630 / r740 / r740xd |
20 | no | Conservative — iDRAC9 behavior likely similar to gen 13 but not verified. |
default |
20 | — | Fallback for unknown Dell models. |
Override autodetection with PROFILE=foo. Adding a chassis: drop a profiles/<slug>.env with MIN_FAN and (optionally) the SENSOR_* IPMI sensor mapping. No code change needed. See CONTRIBUTING.md § Adding a chassis profile.
| class | tested | likely works | won't work |
|---|---|---|---|
| Chassis (fan ctrl) | Dell PowerEdge R730xd, R730, R410, XC730xd-12 | R720, R630, R740 (same iDRAC family) | Non-Dell BMCs (Supermicro, HPE, Lenovo — fan controller sleeps, exporters keep running) |
| CPU | Xeon E5 v3/v4 | any with coretemp driver |
— |
| GPUs (passive) | Tesla P4 | T4, M40, P40, A2, L4, A10, RTX 4000 Ada SFF | — |
| GPUs (active) | RTX A5500 | any consumer/workstation card with own fan | — |
| Drives | SATA HDD, SATA SSD, NVMe, MegaRAID passthrough | anything smartctl --scan enumerates |
— |
| OS | Debian, Ubuntu, Unraid | any Linux + Docker | — |
Even on non-Dell hardware, exporters still work — node_exporter, cadvisor, smartctl_exporter, nvidia_gpu_exporter all run. Only the fan-controller and ipmi_exporter self-disable.
Does it work on non-Dell hardware?
Yes for everything except fan control. node_exporter, cadvisor, smartctl_exporter, nvidia_gpu_exporter, vmagent, unraid-disks, and apt-status all run on any Linux + Docker host. The fan controller refuses to start on non-Dell BMCs (it issues Dell-specific 0x30 0x30 raw IPMI commands and won't try them blindly on other vendors) and ipmi_exporter self-disables without /dev/ipmi0. Same image, everything else still works.
Why one container instead of N? One image to update, one restart unit, one compose to paste per new host, no per-exporter mount duplication. s6-overlay still supervises each sub-process individually — a crashed exporter is restarted in isolation. Full reasoning in Architecture rationale.
How do I add a new chassis profile?
Drop a file at profiles/<slug>.env with at minimum a MIN_FAN value, and optionally SENSOR_* IPMI sensor mappings for the dashboard's per-CPU/inlet/exhaust panels. No code change needed. Full procedure in CONTRIBUTING.md § Adding a chassis profile.
What if my Prometheus needs auth?
Set PROMETHEUS_REMOTE_WRITE_BEARER_TOKEN (for token auth) or the PROMETHEUS_REMOTE_WRITE_USERNAME/_PASSWORD pair (for HTTP basic). Bearer and basic are mutually exclusive. Self-signed cert? Set PROMETHEUS_REMOTE_WRITE_TLS_INSECURE_SKIP_VERIFY=true. See Configuration.
Will this damage my server's fans / void warranty?
The controller writes fan PWM via the standard Dell IPMI raw commands (0x30 0x30 0x01 / 0x30 0x30 0x02) — the same commands documented for ipmitool-based fan control and the same mechanism iDRAC itself uses internally. PWM values are clamped to [MIN_FAN, MAX_FAN] (default 20–100), and per-chassis profiles set a MIN_FAN known not to stall fans on that BMC family (R7xx series the BMC clamps low PWM to a safety RPM anyway; R4xx series the profile sets a higher floor). Worst case if the controller crashes or the container exits: it issues a HandbackAuto IPMI command on shutdown, and even without that, the BMC re-asserts auto mode within ~30s on its own.
How much CPU / memory does it use?
The fan-controller binary is ~2.4 MB and idle CPU is sub-1% on the development hardware. Per-sub-service idle footprint is on the order of single-digit MB resident (node_exporter/cadvisor/vmagent are all Go-static with bounded heaps). Exact numbers depend on number of drives (smartctl scan cost), number of containers (cadvisor watch cost), and scrape interval. Compare to running 6 separate exporter containers — same total cost, one PID 1 supervising it all.
Can I run two of these per host?
You wouldn't want to. They'd race on the IPMI fan setpoint (last one to call SetFan wins, every 15s, in random order — fans flap), both bind :9100 / :8089 / :9290 / etc. and conflict on host network, and both write to /var/lib/host-agent/state and corrupt each other's EWMA. The container is designed to be the one host-agent on a host. For separate metric routing, use vmagent relabeling or a downstream Prometheus federation, not a second container.
Does it work behind a corporate proxy / air-gapped?
vmagent inherits HTTP_PROXY / HTTPS_PROXY / NO_PROXY from the container env, so push behind a proxy works. Air-gapped: pre-pull ghcr.io/mattjackson/host-agent:latest somewhere with internet, push to your internal registry, and set HOST_AGENT_IMAGE to the internal tag. Nothing inside the image reaches out at runtime beyond remote_write.
What about ARM / non-x86?
Currently linux/amd64 only — see .github/workflows/build.yml and the tar -xzf ... amd64.tar.gz calls in the Dockerfile. The Go binary itself is trivially cross-compilable, but the bundled upstream exporters (node_exporter, cadvisor, ipmi_exporter, smartctl_exporter, nvidia_gpu_exporter, vmagent) are fetched as amd64 release tarballs. PRs welcome to multi-arch the fetch step.
Why no go.sum?
Zero external Go dependencies by design. The fan controller is stdlib only, so there's nothing to lock. See CONTRIBUTING.md § What's out of scope — adding import "github.com/..." needs a strong justification, and go.sum will only appear in the repo if that happens.
| Dell stock iDRAC curve | Custom shell + cron | node_exporter alone |
Prometheus + N exporters | host-agent | |
|---|---|---|---|---|---|
| Adaptive PID over time | no | rarely | n/a | n/a | yes (EWMA + v2 intent layer) |
| Per-class control (CPU/GPU/HDD/SSD) | no — single chassis curve | maybe | n/a | n/a | yes |
| Auto-detect chassis | n/a (in BMC) | no | n/a | n/a | yes (dmidecode → profile) |
| Safety floor (proximity-to-emergency) | n/a | rarely | n/a | n/a | yes (per-class ramp) |
| Bundled metrics (node + cadvisor + ipmi + smart + nvidia) | none | usually none | partial (no GPU, no drives, no chassis) | yes (after wiring N containers) | yes |
| One container per host | n/a | n/a (cron script) | yes | no (5-6 containers) | yes |
| Self-disables on missing hardware | n/a | rarely | n/a | per-container, manual | yes (same image runs anywhere) |
| Survives container restart cleanly | n/a | per-script | yes | yes | yes (learned state; observer warms up again) |
| Operational overhead per new host | none | per-host script tweak | one compose | N composes + N image bumps | one compose, one image bump |
| OSS | n/a (vendor firmware) | usually | yes (Apache 2) | yes (Apache 2) | yes (MIT) |
| No extra software | yes | no | no | no | no |
Where stock iDRAC wins: zero install footprint and no operator responsibility. Where it loses: fixed thermal table, no adaptation to the actual chassis airflow or the actual workload pattern, ramps loud the moment a third-party PCIe card confuses its thermal table (the "100% fans randomly" iDRAC problem this project was built to fix).
The cloud-native default is one container per concern. For a single-node fleet that pattern is mostly overhead:
- One image to update. Bump the tag → every host's Watchtower picks it up. No 5x image pulls, no drift between containers.
- One restart unit per host. s6 supervises each sub-process individually — a crashed exporter is restarted in isolation — but the operator-facing unit is a single container.
- One compose to paste. Adding a new host = paste 15 lines. Adding a new sub-process to the agent = no compose change on any host.
- No cross-container coordination. Sub-services share the container's view of
/dev,/sys,/proc,/run/docker.sock— no per-exporter mount duplication.
Tradeoff: a leaking sub-process shares memory pressure with its siblings (unified cgroup). For these workloads (all <1% CPU and <50 MB resident at idle), that's a non-issue.
Logs (s6 prefixes each line with the sub-service):
docker logs host-agent --tail 100 -fController state:
sudo cat /var/lib/host-agent/state/base
# base_speed=22.4515 ← EWMA of equilibrium fan speed
# last_speed=45 ← actual fan speed at last write
# samples=109 ← cycles since restart
# last_updated=…Adaptive state (only when HOST_AGENT_MODE is set):
sudo cat /var/lib/host-agent/state/adaptive.json
# per-class target + deadband, with last-change directionTo reset adaptive targets to mode-initial (e.g. after upgrading or switching modes):
sudo docker stop host-agent
sudo rm /var/lib/host-agent/state/adaptive.json
sudo docker start host-agentRaw observer samples are held in RAM and are rebuilt after restart; there is no observer.json file to clear.
Per-host tuning (advanced): drop env vars in .env next to the compose (e.g. CPU_TARGET=72 to run quieter). Container env beats profile beats default. Most users should never need this — the chassis profile auto-loads sane defaults, and HOST_AGENT_MODE covers the "I want quieter / cooler" intent without per-class numbers.
See CONTRIBUTING.md. TL;DR:
git clone https://github.com/MattJackson/host-agent
cd host-agent
go test ./... # unit + e2e tests; no Docker needed
docker build -t host-agent:dev .The fan controller is pure Go with zero external dependencies — the build is reproducible, the binary is ~2.4 MB, all logic is unit-testable as functions of inputs.
Contributions are welcome. Start with CONTRIBUTING.md for the dev setup, scope, and the "adding a chassis profile" walkthrough, and please review our CODE_OF_CONDUCT.md. CI (go test ./... plus the container build) runs on every push and pull request, so run the tests locally before opening a PR.
Found a vulnerability? Please report it privately — see SECURITY.md for the disclosure process. Don't open a public issue for security reports.
Release history and notable changes are tracked in CHANGELOG.md.