ModbusGo is a comprehensive, production-ready MODBUS protocol implementation in Go that supports both client and server operations. It implements the complete MODBUS Application Protocol Specification V1.1b3, including all standard function codes and advanced features.
- Complete Protocol Support: All 19 standard MODBUS function codes
- Multiple Transports: TCP/IP, RTU (Serial), and ASCII
- Concurrent Safe: Thread-safe operations with proper synchronization
- Extensible Architecture: Clean interfaces for custom implementations
- Auto-Reconnect: Automatic connection recovery on failure
- Broadcast Support: Send commands to all devices (slave ID 0)
- Graceful Shutdown: Server shutdown with timeout and proper cleanup
- Production Ready: Comprehensive error handling and recovery
- Well Tested: Extensive test coverage for all components
go get github.com/adibhanna/modbus-goThe library is organized into several key packages:
modbusgo/
├── modbus/ # Core types, interfaces, and constants
│ ├── constants.go # MODBUS protocol constants
│ └── types.go # Core type definitions
├── pdu/ # Protocol Data Unit handling
│ ├── pdu.go # PDU structure and methods
│ ├── requests.go # Request builders
│ └── responses.go # Response parsers
├── transport/ # Transport layer implementations
│ ├── tcp.go # TCP/IP transport
│ ├── serial.go # RTU/ASCII serial transport
│ └── interface.go # Transport interfaces
├── client.go # MODBUS client implementation
├── server.go # MODBUS server implementation
└── types.go # Package-level type exports
- Separation of Concerns: Clear separation between protocol logic, transport, and business logic
- Interface-Based: Core components use interfaces for flexibility
- Zero Dependencies: Minimal external dependencies (only standard library where possible)
- Type Safety: Strong typing throughout the codebase
- Error Propagation: Explicit error handling at all levels
package main
import (
"fmt"
"log"
modbus "github.com/adibhanna/modbus-go"
)
func main() {
// Connect to MODBUS TCP server
client := modbus.NewTCPClient("localhost:502")
client.SetSlaveID(1)
defer client.Close()
// Read holding registers
values, err := client.ReadHoldingRegisters(0, 10)
if err != nil {
log.Fatal(err)
}
fmt.Printf("Register values: %v\n", values)
}package main
import (
"log"
modbus "github.com/adibhanna/modbus-go"
)
func main() {
// Create data store
dataStore := modbus.NewDefaultDataStore(10000, 10000, 10000, 10000)
// Initialize some data
dataStore.SetHoldingRegister(0, 100)
dataStore.SetCoil(0, true)
// Start server
server, err := modbus.NewTCPServer(":502", dataStore)
if err != nil {
log.Fatal(err)
}
log.Println("Server starting on :502")
if err := server.Start(); err != nil {
log.Fatal(err)
}
}ModbusGo provides flexible configuration options for clients, supporting both programmatic configuration and JSON-based configuration files. This allows you to adapt the library to different devices, environments, and operational requirements.
The library supports multiple levels of configuration:
- Core Library Configuration - Simple, lightweight JSON configuration built into the core library
- Extended Configuration System - Comprehensive configuration with device profiles, testing parameters, and advanced options
- Runtime Configuration - Dynamic configuration changes during execution
- Configuration Persistence - Save and load configuration settings
The core library supports a simple JSON configuration format:
{
"slave_id": 1,
"timeout_ms": 10000,
"retry_count": 3,
"retry_delay_ms": 100,
"connect_timeout_ms": 5000,
"transport_type": "tcp"
}| Parameter | Type | Default | Description |
|---|---|---|---|
slave_id |
int | 1 | MODBUS slave/unit identifier |
timeout_ms |
int | 1000 | Response timeout in milliseconds |
retry_count |
int | 3 | Number of retry attempts on failure |
retry_delay_ms |
int | 100 | Delay between retry attempts in milliseconds |
connect_timeout_ms |
int | 5000 | Connection timeout in milliseconds |
transport_type |
string | "tcp" | Transport protocol ("tcp", "rtu", "ascii") |
// Load configuration from file
client, err := modbus.NewTCPClientFromJSONFile("config.json", "192.168.1.102:502")
if err != nil {
log.Fatal(err)
}// Load configuration from JSON string
jsonConfig := `{
"slave_id": 2,
"timeout_ms": 15000,
"retry_count": 5,
"retry_delay_ms": 250,
"connect_timeout_ms": 8000,
"transport_type": "tcp"
}`
client, err := modbus.NewTCPClientFromJSONString(jsonConfig, "192.168.1.102:502")
if err != nil {
log.Fatal(err)
}// Create configuration struct
config := modbus.DefaultClientConfig()
config.SlaveID = 3
config.Timeout = 20 * time.Second
config.RetryCount = 1
config.RetryDelay = 500 * time.Millisecond
// Create client from config
client := modbus.NewTCPClientFromConfig(config, "192.168.1.102:502")client := modbus.NewTCPClient("192.168.1.102:502")
// Get current configuration
config := client.GetConfig()
fmt.Printf("Current SlaveID: %d\n", config.SlaveID)
fmt.Printf("Current Timeout: %v\n", config.Timeout)// Individual parameter changes
client.SetSlaveID(5)
client.SetTimeout(15 * time.Second)
client.SetRetryCount(2)
client.SetRetryDelay(200 * time.Millisecond)
client.SetConnectTimeout(10 * time.Second)
// Bulk configuration change
newConfig := modbus.DefaultClientConfig()
newConfig.SlaveID = 10
newConfig.RetryCount = 5
client.ApplyConfig(newConfig)// Save configuration to JSON file
config := client.GetConfig()
err := config.SaveClientConfigToJSON("saved-config.json")
if err != nil {
log.Printf("Failed to save config: %v", err)
}
// Convert configuration to JSON string
jsonString, err := config.ToJSONString()
if err != nil {
log.Printf("Failed to convert config: %v", err)
} else {
fmt.Printf("Configuration:\n%s\n", jsonString)
}For comprehensive testing, device profiles, and advanced configuration management, use the extended configuration system:
import "github.com/adibhanna/modbus-go/config"
// Load extended configuration
cfg, err := config.LoadConfig("extended-config.json")
if err != nil {
log.Fatal(err)
}
// Create client using extended configuration
client := modbus.NewTCPClient(cfg.Connection.GetFullAddress())
client.SetSlaveID(cfg.Modbus.GetSlaveID())
client.SetTimeout(cfg.Connection.GetTimeout())
client.SetRetryCount(cfg.Connection.RetryCount){
"connection": {
"address": "192.168.1.102",
"port": 502,
"timeout_ms": 10000,
"connect_timeout_ms": 5000,
"retry_count": 3,
"transport_type": "tcp"
},
"modbus": {
"slave_id": 1,
"unit_id": 1,
"protocol_id": 0
},
"testing": {
"enabled_tests": [
"read_holding_registers",
"read_coils",
"write_single_register"
],
"test_addresses": {
"holding_registers": {
"start_address": 0,
"quantity": 5
}
}
},
"device_profiles": {
"schneider_electric": {
"slave_id": 1,
"holding_registers_start": 1,
"supported_functions": [1, 2, 3, 4, 5, 6, 15, 16]
}
},
"current_profile": "schneider_electric"
}{
"slave_id": 1,
"timeout_ms": 10000,
"retry_count": 3,
"retry_delay_ms": 100,
"connect_timeout_ms": 5000,
"transport_type": "tcp"
}{
"slave_id": 1,
"timeout_ms": 8000,
"retry_count": 2,
"retry_delay_ms": 150,
"connect_timeout_ms": 4000,
"transport_type": "tcp"
}{
"slave_id": 1,
"timeout_ms": 5000,
"retry_count": 1,
"retry_delay_ms": 200,
"connect_timeout_ms": 3000,
"transport_type": "tcp"
}// Development environment
devConfig := `{
"slave_id": 1,
"timeout_ms": 30000,
"retry_count": 5,
"retry_delay_ms": 1000
}`
// Production environment
prodConfig := `{
"slave_id": 1,
"timeout_ms": 5000,
"retry_count": 2,
"retry_delay_ms": 100
}`
var configStr string
if os.Getenv("ENV") == "production" {
configStr = prodConfig
} else {
configStr = devConfig
}
client, err := modbus.NewTCPClientFromJSONString(configStr, address)client, err := modbus.NewTCPClientFromJSONFile("config.json", address)
if err != nil {
// Fallback to default configuration
log.Printf("Failed to load config, using defaults: %v", err)
client = modbus.NewTCPClient(address)
}
// Validate configuration
config := client.GetConfig()
if config.Timeout < 1*time.Second {
log.Printf("Warning: Timeout very low (%v), consider increasing", config.Timeout)
}
if config.RetryCount > 10 {
log.Printf("Warning: High retry count (%d) may cause delays", config.RetryCount)
}// Base configuration template
func NewIndustrialConfig() *modbus.ClientConfig {
config := modbus.DefaultClientConfig()
config.Timeout = 10 * time.Second
config.RetryCount = 3
config.RetryDelay = 500 * time.Millisecond
config.ConnectTimeout = 15 * time.Second
return config
}
// Device-specific adjustments
func NewSchneiderzConfig() *modbus.ClientConfig {
config := NewIndustrialConfig()
config.SlaveID = 1
config.RetryDelay = 100 * time.Millisecond
return config
}If you're upgrading from a previous version that didn't support configuration:
client := modbus.NewTCPClient("192.168.1.102:502")
client.SetSlaveID(1)
client.SetTimeout(10 * time.Second)
client.SetRetryCount(3)// Save existing configuration as JSON template
config := &modbus.ClientConfig{
SlaveID: 1,
Timeout: 10 * time.Second,
RetryCount: 3,
RetryDelay: 100 * time.Millisecond,
ConnectTimeout: 5 * time.Second,
TransportType: modbus.TransportTCP,
}
// Save as template for future use
err := config.SaveClientConfigToJSON("my-device-config.json")
// Load from file in future
client, err := modbus.NewTCPClientFromJSONFile("my-device-config.json", "192.168.1.102:502")The client supports automatic reconnection when the connection is lost:
client := modbus.NewTCPClient("192.168.1.100:502")
client.SetSlaveID(1)
defer client.Close()
// Enable auto-reconnect
client.SetAutoReconnect(true)
// Now if the connection is lost during operations,
// the client will automatically attempt to reconnect
values, err := client.ReadHoldingRegisters(0, 10)
if err != nil {
// Error only occurs if reconnect also fails
log.Printf("Failed after reconnect attempt: %v", err)
}
// Check auto-reconnect status
if client.GetAutoReconnect() {
log.Println("Auto-reconnect is enabled")
}MODBUS supports broadcast messages (slave ID 0) for write operations where no response is expected:
client := modbus.NewTCPClient("192.168.1.100:502")
client.SetSlaveID(1)
defer client.Close()
// Broadcast write single coil to all devices
err := client.BroadcastWriteSingleCoil(0, true)
// Broadcast write single register to all devices
err = client.BroadcastWriteSingleRegister(100, 1234)
// Broadcast write multiple coils to all devices
err = client.BroadcastWriteMultipleCoils(0, []bool{true, false, true, true})
// Broadcast write multiple registers to all devices
err = client.BroadcastWriteMultipleRegisters(100, []uint16{1, 2, 3, 4})Note: Broadcast messages do not receive responses. They are useful for:
- Synchronizing multiple devices simultaneously
- Emergency stops across all devices
- System-wide configuration changes
- Resetting all devices to a known state
The TCP server supports graceful shutdown with configurable timeout:
// Create and start server
server, _ := modbus.NewTCPServer(":502", dataStore)
go func() {
if err := server.Start(); err != nil {
log.Printf("Server error: %v", err)
}
}()
// ... server runs ...
// Option 1: Simple stop (waits for all connections to close)
err := server.Stop()
// Option 2: Stop with timeout (returns error if timeout exceeded)
err = server.StopWithTimeout(5 * time.Second)
if err != nil {
log.Printf("Server shutdown timed out: %v", err)
// Connections were forcibly closed after timeout
}Complete support for all MODBUS diagnostic functions:
// Get communication event counter (FC 0x0B)
status, eventCount, err := client.GetCommEventCounter()
// status: 0xFFFF = ready, 0x0000 = not ready
// eventCount: number of successful message completions
fmt.Printf("Status: 0x%04X, Events: %d\n", status, eventCount)
// Get communication event log (FC 0x0C)
status, eventCount, messageCount, events, err := client.GetCommEventLog()
// events: byte array of event codes
fmt.Printf("Messages: %d, Events: %d\n", messageCount, eventCount)
for i, ev := range events {
fmt.Printf("Event %d: 0x%02X\n", i, ev)
}
// Report server ID (FC 0x11)
serverData, err := client.ReportServerID()
// serverData includes run indicator and server-specific identification
fmt.Printf("Server ID data: %v\n", serverData)
if len(serverData) > 0 {
runIndicator := serverData[0] // 0xFF = ON, 0x00 = OFF
fmt.Printf("Run indicator: 0x%02X\n", runIndicator)
}RTU and ASCII transports now include mutex protection for thread safety:
// RTU transport is safe for concurrent use
rtuTransport := transport.NewRTUTransport(config)
// Multiple goroutines can safely use the same transport
var wg sync.WaitGroup
for i := 0; i < 10; i++ {
wg.Add(1)
go func(id int) {
defer wg.Done()
// Safe concurrent access
resp, err := rtuTransport.SendRequest(1, request)
// ...
}(i)
}
wg.Wait()The library provides convenient methods for reading and writing multi-register data types:
client := modbus.NewTCPClient("192.168.1.100:502")
client.SetSlaveID(1)
defer client.Close()
// Read/Write 32-bit integers (uses 2 registers)
val32, err := client.ReadUint32(100)
err = client.WriteUint32(100, 12345678)
// Read/Write 64-bit integers (uses 4 registers)
val64, err := client.ReadUint64(200)
err = client.WriteUint64(200, 123456789012345)
// Read/Write 32-bit floats
floatVal, err := client.ReadFloat32(300)
err = client.WriteFloat32(300, 3.14159)
// Read/Write 64-bit floats
float64Val, err := client.ReadFloat64(400)
err = client.WriteFloat64(400, 3.141592653589793)
// Read/Write signed integers
int32Val, err := client.ReadInt32(500)
err = client.WriteInt32(500, -12345)
// Read/Write multiple values at once
uint32s, err := client.ReadUint32s(600, 5) // Read 5 uint32 values
err = client.WriteFloat32s(700, []float32{1.1, 2.2, 3.3})
// Read/Write raw bytes
bytes, err := client.ReadBytes(800, 20) // Read 20 bytes
err = client.WriteBytes(800, []byte{0x01, 0x02, 0x03, 0x04})
// Read/Write strings
str, err := client.ReadString(900, 32) // Read up to 32 chars
err = client.WriteString(900, "Hello MODBUS", 32)
// Single register/coil read helpers
coilVal, err := client.ReadCoil(0) // Read single coil
discreteVal, err := client.ReadDiscreteInput(0) // Read single discrete input
regVal, err := client.ReadHoldingRegister(0) // Read single holding register
inputVal, err := client.ReadInputRegister(0) // Read single input register
// Read from input registers
inputFloat, err := client.ReadInputFloat32(1000)
inputUint32, err := client.ReadInputUint32(1000)Different devices use different byte/word ordering. Configure the encoding to match your device:
client := modbus.NewTCPClient("192.168.1.100:502")
client.SetSlaveID(1)
// Default is Big Endian, High Word First (most common in MODBUS)
// This is the standard MODBUS byte order
// For devices using different byte ordering:
client.SetEncoding(modbus.LittleEndian, modbus.HighWordFirst)
// Or for different word ordering:
client.SetEncoding(modbus.BigEndian, modbus.LowWordFirst)
// Check current encoding
enc := client.GetEncoding()
fmt.Printf("Byte Order: %v, Word Order: %v\n", enc.ByteOrder, enc.WordOrder)
// Encoding affects all multi-byte operations:
// - ReadUint32/WriteUint32
// - ReadFloat32/WriteFloat32
// - ReadUint64/WriteUint64
// - ReadFloat64/WriteFloat64
// - ReadBytes/WriteBytes
// - ReadString/WriteStringCommon device encoding configurations:
| Device/Manufacturer | Byte Order | Word Order |
|---|---|---|
| Most MODBUS devices | BigEndian | HighWordFirst |
| Some Siemens PLCs | BigEndian | LowWordFirst |
| Some ABB devices | LittleEndian | HighWordFirst |
Secure your MODBUS TCP communications with TLS encryption:
import (
"crypto/tls"
"crypto/x509"
"io/ioutil"
"github.com/adibhanna/modbus-go/transport"
)
// Basic TLS with server certificate verification
tlsConfig := &tls.Config{
MinVersion: tls.VersionTLS12,
}
tcpTransport := transport.NewTLSTransport("192.168.1.100:802", tlsConfig)
if err := tcpTransport.Connect(); err != nil {
log.Fatal(err)
}
defer tcpTransport.Close()
// With client certificate authentication (mutual TLS)
cert, err := tls.LoadX509KeyPair("client-cert.pem", "client-key.pem")
if err != nil {
log.Fatal(err)
}
caCert, err := ioutil.ReadFile("ca-cert.pem")
if err != nil {
log.Fatal(err)
}
caCertPool := x509.NewCertPool()
caCertPool.AppendCertsFromPEM(caCert)
tlsConfig := &tls.Config{
Certificates: []tls.Certificate{cert},
RootCAs: caCertPool,
MinVersion: tls.VersionTLS12,
}
secureTransport := transport.NewTLSTransport("192.168.1.100:802", tlsConfig)
// Skip certificate verification (NOT recommended for production)
insecureConfig := &tls.Config{
InsecureSkipVerify: true,
}For serial-to-Ethernet converters that use RTU framing over TCP (not standard MODBUS TCP):
import "github.com/adibhanna/modbus-go/transport"
// RTU over TCP uses RTU framing (slave ID + PDU + CRC) over TCP connection
// This is common with serial-to-Ethernet gateways that don't translate to MODBUS TCP
rtuOverTCP := transport.NewRTUOverTCPTransport("192.168.1.100:4001")
if err := rtuOverTCP.Connect(); err != nil {
log.Fatal(err)
}
defer rtuOverTCP.Close()
// Create client with RTU over TCP transport
client := modbus.NewClient(rtuOverTCP)
client.SetSlaveID(1)
// Use normally - the transport handles RTU framing over TCP
values, err := client.ReadHoldingRegisters(0, 10)When to use RTU over TCP:
- Serial-to-Ethernet converters in "raw" or "transparent" mode
- Devices that expect RTU framing regardless of transport
- Legacy systems upgraded with Ethernet adapters
For MODBUS over UDP (less reliable but lower latency):
import "github.com/adibhanna/modbus-go/transport"
// MODBUS over UDP - uses MBAP header like TCP but over UDP
udpTransport := transport.NewUDPTransport("192.168.1.100:502")
if err := udpTransport.Connect(); err != nil {
log.Fatal(err)
}
defer udpTransport.Close()
// Create client with UDP transport
client := modbus.NewClient(udpTransport)
client.SetSlaveID(1)
// Use normally
values, err := client.ReadHoldingRegisters(0, 10)UDP considerations:
- No automatic retransmission of lost packets
- No ordering guarantee
- Lower latency than TCP
- Useful for non-critical, high-frequency polling
- Configure appropriate timeout and retry settings
Configure automatic connection cleanup after periods of inactivity:
import "github.com/adibhanna/modbus-go/transport"
tcpTransport := transport.NewTCPTransport("192.168.1.100:502")
// Set idle timeout - connection will be closed after 5 minutes of inactivity
tcpTransport.SetIdleTimeout(5 * time.Minute)
// Check current idle timeout
idleTimeout := tcpTransport.GetIdleTimeout()
// Set connect timeout separately
tcpTransport.SetConnectTimeout(10 * time.Second)Add custom logging for debugging and monitoring:
import "github.com/adibhanna/modbus-go/transport"
// Logger interface - implement Printf method
type MyLogger struct{}
func (l *MyLogger) Printf(format string, v ...interface{}) {
log.Printf("[MODBUS] "+format, v...)
}
// Set logger on transport
tcpTransport := transport.NewTCPTransport("192.168.1.100:502")
tcpTransport.SetLogger(&MyLogger{})
// Also works with RTU over TCP and UDP transports
rtuOverTCP := transport.NewRTUOverTCPTransport("192.168.1.100:4001")
rtuOverTCP.SetLogger(&MyLogger{})
udpTransport := transport.NewUDPTransport("192.168.1.100:502")
udpTransport.SetLogger(&MyLogger{})
// Use standard log package
type StdLogger struct{}
func (l *StdLogger) Printf(format string, v ...interface{}) {
log.Printf(format, v...)
}MODBUS defines four primary data types:
| Data Type | Access | Size | Address Range | Description |
|---|---|---|---|---|
| Coils | Read/Write | 1 bit | 0-65535 | Discrete outputs |
| Discrete Inputs | Read Only | 1 bit | 0-65535 | Discrete inputs |
| Holding Registers | Read/Write | 16 bits | 0-65535 | General purpose registers |
| Input Registers | Read Only | 16 bits | 0-65535 | Input data registers |
MODBUS uses 16-bit addressing (0-65535). The library uses zero-based addressing internally:
// Address type ensures type safety
var addr modbus.Address = 100 // Register at address 100
// Quantity type for counts
var qty modbus.Quantity = 10 // Read 10 registersThe PDU is the core protocol message structure:
[Function Code: 1 byte] [Data: 0-252 bytes]
Maximum PDU size is 253 bytes.
The ADU includes transport-specific framing:
TCP/IP ADU:
[MBAP Header: 7 bytes] [PDU: up to 253 bytes]
Serial RTU ADU:
[Address: 1 byte] [PDU: up to 253 bytes] [CRC: 2 bytes]
Reads the status of discrete outputs (coils).
// Read 10 coils starting at address 100
values, err := client.ReadCoils(100, 10)
// values is []boolReads the status of discrete inputs.
// Read 8 discrete inputs starting at address 0
values, err := client.ReadDiscreteInputs(0, 8)
// values is []boolReads multiple holding registers.
// Read 5 holding registers starting at address 1000
values, err := client.ReadHoldingRegisters(1000, 5)
// values is []uint16Reads multiple input registers.
// Read 3 input registers starting at address 500
values, err := client.ReadInputRegisters(500, 3)
// values is []uint16Writes a single coil.
// Turn on coil at address 10
err := client.WriteSingleCoil(10, true)Writes a single holding register.
// Write value 12345 to register 100
err := client.WriteSingleRegister(100, 12345)Writes multiple coils.
// Write coil values starting at address 20
values := []bool{true, false, true, true, false}
err := client.WriteMultipleCoils(20, values)Writes multiple holding registers.
// Write register values starting at address 200
values := []uint16{100, 200, 300, 400}
err := client.WriteMultipleRegisters(200, values)Modifies a register using AND/OR masks.
// address: 100, AND mask: 0x00F0, OR mask: 0x0025
// Result = (current_value AND 0x00F0) OR 0x0025
err := client.MaskWriteRegister(100, 0x00F0, 0x0025)Atomic read and write operation.
// Read 5 registers from address 100, write 3 values to address 200
writeValues := []uint16{111, 222, 333}
readValues, err := client.ReadWriteMultipleRegisters(100, 5, 200, writeValues)Reads device exception status (8 bits).
status, err := client.ReadExceptionStatus()
// status is uint8, each bit indicates an exceptionVarious diagnostic subfunctions for serial line diagnostics.
// Echo test - returns the same data
result, err := client.Diagnostic(modbus.DiagSubReturnQueryData, []byte{0x12, 0x34})
// Clear counters
_, err := client.Diagnostic(modbus.DiagSubClearCounters, nil)
// Get bus message count
result, err := client.Diagnostic(modbus.DiagSubReturnBusMessageCount, nil)Available diagnostic subfunctions:
DiagSubReturnQueryData(0x0000): Echo testDiagSubRestartCommOption(0x0001): Restart communicationsDiagSubReturnDiagRegister(0x0002): Return diagnostic registerDiagSubForceListenOnlyMode(0x0004): Force listen-only modeDiagSubClearCounters(0x000A): Clear all countersDiagSubReturnBusMessageCount(0x000B): Get bus message countDiagSubReturnBusCommErrorCount(0x000C): Get communication errorsDiagSubReturnBusExceptionCount(0x000D): Get exception errorsDiagSubReturnServerMessageCount(0x000E): Get server messagesDiagSubReturnServerNoRespCount(0x000F): Get no response count
Retrieves communication event counter.
status, eventCount, err := client.GetCommEventCounter()
// status: 0xFFFF = ready, 0x0000 = not ready
// eventCount: number of successful message interactionsRetrieves communication event log.
status, eventCount, messageCount, events, err := client.GetCommEventLog()
// events is []byte containing the event logRetrieves server identification and status.
serverID, runIndicator, additionalData, err := client.ReportServerID()
// serverID: []byte with server identification string
// runIndicator: 0xFF = ON, 0x00 = OFFReads file records from extended memory.
// Define records to read
records := []modbus.FileRecord{
{
ReferenceType: modbus.FileRecordTypeExtended, // Must be 0x06
FileNumber: 4, // File number (0-65535)
RecordNumber: 1, // Starting record (0-9999)
RecordLength: 2, // Number of registers to read
},
}
// Read the records
result, err := client.ReadFileRecords(records)
// result[0].RecordData contains the register valuesWrites file records to extended memory.
// Define records to write
records := []modbus.FileRecord{
{
ReferenceType: modbus.FileRecordTypeExtended,
FileNumber: 4,
RecordNumber: 1,
RecordLength: 2,
RecordData: []uint16{0x1234, 0x5678}, // Data to write
},
}
err := client.WriteFileRecords(records)Reads FIFO queue contents.
// Read FIFO queue at pointer address 1000
values, err := client.ReadFIFOQueue(1000)
// values is []uint16 with up to 31 valuesUsed for device identification and other encapsulated protocols.
// Read basic device identification
vendorName, productCode, version, err := client.ReadDeviceIdentification(
modbus.DeviceIDReadBasic, // Read level
0x00, // Object ID
)// Basic TCP client
client := modbus.NewTCPClient("192.168.1.100:502")
client.SetSlaveID(1)
// With custom configuration
config := modbus.ClientConfig{
SlaveID: 1,
Timeout: 5 * time.Second,
RetryCount: 3,
}
client, err := modbus.NewTCPClientWithConfig("192.168.1.100:502", config)// RTU client
client, err := modbus.NewRTUClient("/dev/ttyUSB0", 1, 9600, 8, 1, modbus.ParityNone)
// With custom config
serialConfig := modbus.SerialConfig{
Device: "/dev/ttyUSB0",
BaudRate: 19200,
DataBits: 8,
StopBits: 1,
Parity: modbus.ParityEven,
Timeout: 3 * time.Second,
}
client, err := modbus.NewRTUClientWithConfig(serialConfig, 1)- Connection Management
// Always close connections
defer client.Close()
// Check connection before operations
if !client.IsConnected() {
err := client.Connect()
}- Error Handling
values, err := client.ReadHoldingRegisters(100, 10)
if err != nil {
if modbusErr, ok := err.(*modbus.ModbusError); ok {
// Handle MODBUS-specific errors
switch modbusErr.ExceptionCode {
case modbus.ExceptionCodeIllegalDataAddress:
// Handle invalid address
case modbus.ExceptionCodeServerDeviceBusy:
// Retry later
}
}
// Handle other errors
}- Bulk Operations
// Efficient: Read all at once
values, err := client.ReadHoldingRegisters(0, 100)
// Inefficient: Multiple small reads
for i := 0; i < 100; i++ {
value, err := client.ReadHoldingRegisters(i, 1) // Avoid this
}// Create data store
dataStore := modbus.NewDefaultDataStore(
10000, // Number of coils
10000, // Number of discrete inputs
10000, // Number of holding registers
10000, // Number of input registers
)
// Create and start server
server, err := modbus.NewTCPServer(":502", dataStore)
if err != nil {
log.Fatal(err)
}
// Start in blocking mode
err = server.Start()
// Or start in background
go func() {
if err := server.Start(); err != nil {
log.Fatal(err)
}
}()Implement the DataStore interface for custom storage:
type CustomDataStore struct {
// Your storage implementation
db *sql.DB
}
func (ds *CustomDataStore) ReadHoldingRegisters(address modbus.Address, quantity modbus.Quantity) ([]uint16, error) {
// Read from database
values := make([]uint16, quantity)
rows, err := ds.db.Query("SELECT value FROM registers WHERE address >= ? LIMIT ?", address, quantity)
// ... process rows
return values, nil
}
func (ds *CustomDataStore) WriteHoldingRegisters(address modbus.Address, values []uint16) error {
// Write to database
tx, err := ds.db.Begin()
// ... insert/update values
return tx.Commit()
}
// Implement other required methods...// Custom device identification
handler := modbus.NewServerRequestHandler(dataStore)
handler.SetDeviceIdentification(&modbus.DeviceIdentification{
VendorName: "Your Company",
ProductCode: "PROD-001",
MajorMinorRevision: "1.0.0",
VendorURL: "https://example.com",
ProductName: "Industrial Controller",
ModelName: "IC-2024",
UserApplicationName: "Process Control",
ConformityLevel: modbus.ConformityLevelBasicStream,
})// Monitor server events
type ServerMonitor struct {
server *modbus.Server
stats struct {
requests uint64
errors uint64
lastError error
}
}
func (m *ServerMonitor) Start() {
ticker := time.NewTicker(5 * time.Second)
for range ticker.C {
// Log statistics
log.Printf("Requests: %d, Errors: %d", m.stats.requests, m.stats.errors)
// Update diagnostic counters
dataStore.IncrementDiagnosticCounter("ServerMessage")
}
}File records provide access to extended memory beyond the 65536 address limit:
// Server-side: Initialize file records
records := []modbus.FileRecord{
{
ReferenceType: modbus.FileRecordTypeExtended,
FileNumber: 1, // File 1
RecordNumber: 0, // Record 0
RecordLength: 100, // 100 registers
RecordData: data, // Your data
},
}
dataStore.WriteFileRecords(records)
// Client-side: Read file records
readReq := []modbus.FileRecord{
{
ReferenceType: modbus.FileRecordTypeExtended,
FileNumber: 1,
RecordNumber: 0,
RecordLength: 100,
},
}
result, err := client.ReadFileRecords(readReq)FIFO queues are useful for buffering time-series data:
// Server-side: Manage FIFO queue
type FIFOManager struct {
dataStore *modbus.DefaultDataStore
address modbus.Address
maxSize int
}
func (f *FIFOManager) Push(value uint16) error {
current, _ := f.dataStore.ReadFIFOQueue(f.address)
if len(current) >= f.maxSize {
current = current[1:] // Remove oldest
}
current = append(current, value)
return f.dataStore.WriteFIFOQueue(f.address, current)
}
// Client-side: Read FIFO
values, err := client.ReadFIFOQueue(1000)
for i, v := range values {
fmt.Printf("Entry %d: %d\n", i, v)
}Implement comprehensive diagnostics for troubleshooting:
// Server-side: Track diagnostics
func trackDiagnostics(ds *modbus.DefaultDataStore, req *pdu.Request, resp *pdu.Response) {
ds.IncrementDiagnosticCounter("BusMessage")
if resp.IsException() {
ds.IncrementDiagnosticCounter("BusException")
ds.SetExceptionStatus(0xFF) // Set exception flag
}
if resp == nil {
ds.IncrementDiagnosticCounter("ServerNoResp")
}
}
// Client-side: Monitor link quality
func monitorLink(client modbus.Client) {
// Echo test
testData := []byte{0xAA, 0x55}
result, err := client.Diagnostic(modbus.DiagSubReturnQueryData, testData)
if err != nil || !bytes.Equal(result, testData) {
log.Println("Link quality issue detected")
}
// Get error counts
status, count, err := client.GetCommEventCounter()
if count > lastCount {
successRate := float64(count-errorCount) / float64(count) * 100
log.Printf("Success rate: %.2f%%\n", successRate)
}
}TCP transport uses the MODBUS TCP protocol with MBAP header:
// MBAP Header Structure
type MBAPHeader struct {
TransactionID uint16 // Transaction identifier
ProtocolID uint16 // Always 0 for MODBUS
Length uint16 // Number of following bytes
UnitID uint8 // Unit identifier (slave ID)
}
// Custom TCP transport options
transport := transport.NewTCPTransport(transport.TCPConfig{
Address: "192.168.1.100:502",
ConnectTimeout: 5 * time.Second,
ReadTimeout: 3 * time.Second,
WriteTimeout: 3 * time.Second,
KeepAlive: 30 * time.Second,
MaxConnections: 10,
})RTU uses binary encoding with CRC error checking:
// RTU Frame Structure
type RTUFrame struct {
SlaveID uint8 // Device address
FunctionCode uint8 // Function code
Data []byte // Data bytes
CRC uint16 // CRC-16 checksum
}
// Calculate CRC for RTU
func calculateCRC(data []byte) uint16 {
crc := uint16(0xFFFF)
for _, b := range data {
crc ^= uint16(b)
for i := 0; i < 8; i++ {
if crc&0x0001 != 0 {
crc = (crc >> 1) ^ 0xA001
} else {
crc >>= 1
}
}
}
return crc
}ASCII uses text encoding with LRC error checking:
// ASCII Frame Structure
type ASCIIFrame struct {
Start byte // ':' character
SlaveID [2]byte // Two ASCII hex chars
FunctionCode [2]byte // Two ASCII hex chars
Data []byte // ASCII hex pairs
LRC [2]byte // LRC checksum
End [2]byte // CR LF
}
// Calculate LRC for ASCII
func calculateLRC(data []byte) uint8 {
var lrc uint8
for _, b := range data {
lrc += b
}
return uint8(-int8(lrc))
}The library defines standard MODBUS exception codes:
| Code | Name | Description |
|---|---|---|
| 0x01 | Illegal Function | Function code not supported |
| 0x02 | Illegal Data Address | Invalid address or address range |
| 0x03 | Illegal Data Value | Invalid value in data field |
| 0x04 | Server Device Failure | Unrecoverable error occurred |
| 0x05 | Acknowledge | Long duration command acknowledged |
| 0x06 | Server Device Busy | Device busy, retry later |
| 0x08 | Memory Parity Error | Memory parity error detected |
| 0x0A | Gateway Path Unavailable | Gateway misconfigured |
| 0x0B | Gateway Target Failed | Target device failed to respond |
// MODBUS protocol error
type ModbusError struct {
FunctionCode FunctionCode
ExceptionCode ExceptionCode
Message string
}
// Transport error
type TransportError struct {
Operation string
Cause error
}
// Timeout error
type TimeoutError struct {
Operation string
Duration time.Duration
}// Comprehensive error handling
func robustRead(client modbus.Client, address modbus.Address, count modbus.Quantity) ([]uint16, error) {
maxRetries := 3
backoff := 100 * time.Millisecond
for retry := 0; retry < maxRetries; retry++ {
values, err := client.ReadHoldingRegisters(address, count)
if err == nil {
return values, nil
}
// Check error type
switch e := err.(type) {
case *modbus.ModbusError:
if e.ExceptionCode == modbus.ExceptionCodeServerDeviceBusy {
// Device busy, wait and retry
time.Sleep(backoff)
backoff *= 2
continue
}
// Other MODBUS errors are fatal
return nil, err
case *modbus.TimeoutError:
// Network timeout, retry
log.Printf("Timeout on attempt %d: %v", retry+1, e)
continue
case *modbus.TransportError:
// Transport failure, might need reconnection
if retry < maxRetries-1 {
client.Reconnect()
continue
}
}
return nil, err
}
return nil, fmt.Errorf("failed after %d retries", maxRetries)
}func TestReadHoldingRegisters(t *testing.T) {
// Create mock data store
ds := modbus.NewDefaultDataStore(100, 100, 100, 100)
// Set test data
testData := []uint16{100, 200, 300, 400, 500}
for i, v := range testData {
ds.SetHoldingRegister(modbus.Address(i), v)
}
// Create handler
handler := modbus.NewServerRequestHandler(ds)
// Create request
req := pdu.NewRequest(modbus.FuncCodeReadHoldingRegisters,
append(pdu.EncodeUint16(0), pdu.EncodeUint16(5)...))
// Process request
resp := handler.HandleRequest(1, req)
// Verify response
if resp.FunctionCode != modbus.FuncCodeReadHoldingRegisters {
t.Errorf("Wrong function code: %v", resp.FunctionCode)
}
// Decode response data
if resp.Data[0] != 10 { // Byte count
t.Errorf("Wrong byte count: %d", resp.Data[0])
}
values, _ := pdu.DecodeUint16Slice(resp.Data[1:])
if !reflect.DeepEqual(values, testData) {
t.Errorf("Data mismatch: got %v, want %v", values, testData)
}
}func TestClientServerIntegration(t *testing.T) {
// Setup server
ds := modbus.NewDefaultDataStore(1000, 1000, 1000, 1000)
server, _ := modbus.NewTCPServer(":15502", ds)
go server.Start()
defer server.Stop()
// Wait for server
time.Sleep(100 * time.Millisecond)
// Create client
client := modbus.NewTCPClient("localhost:15502")
client.SetSlaveID(1)
defer client.Close()
// Test write and read
testValues := []uint16{111, 222, 333}
err = client.WriteMultipleRegisters(100, testValues)
if err != nil {
t.Fatal(err)
}
readValues, err := client.ReadHoldingRegisters(100, 3)
if err != nil {
t.Fatal(err)
}
if !reflect.DeepEqual(readValues, testValues) {
t.Errorf("Mismatch: wrote %v, read %v", testValues, readValues)
}
}func BenchmarkReadHoldingRegisters(b *testing.B) {
ds := modbus.NewDefaultDataStore(10000, 10000, 10000, 10000)
handler := modbus.NewServerRequestHandler(ds)
req := pdu.NewRequest(modbus.FuncCodeReadHoldingRegisters,
append(pdu.EncodeUint16(0), pdu.EncodeUint16(100)...))
b.ResetTimer()
for i := 0; i < b.N; i++ {
resp := handler.HandleRequest(1, req)
if resp.IsException() {
b.Fatal("Unexpected exception")
}
}
}
func TestConcurrentAccess(t *testing.T) {
ds := modbus.NewDefaultDataStore(1000, 1000, 1000, 1000)
server, _ := modbus.NewTCPServer(":25502", ds)
go server.Start()
defer server.Stop()
// Create multiple concurrent clients
var wg sync.WaitGroup
errors := make(chan error, 10)
for i := 0; i < 10; i++ {
wg.Add(1)
go func(id int) {
defer wg.Done()
client := modbus.NewTCPClient("localhost:25502")
client.SetSlaveID(uint8(id))
defer client.Close()
// Perform operations
for j := 0; j < 100; j++ {
addr := modbus.Address(id * 100)
value := uint16(id*1000 + j)
err := client.WriteSingleRegister(addr, value)
if err != nil {
errors <- err
return
}
readValue, err := client.ReadHoldingRegisters(addr, 1)
if err != nil {
errors <- err
return
}
if readValue[0] != value {
errors <- fmt.Errorf("Value mismatch")
return
}
}
}(i)
}
wg.Wait()
close(errors)
for err := range errors {
if err != nil {
t.Error(err)
}
}
}-
Batch Operations
- Use multi-register reads/writes instead of single operations
- Maximum efficiency: read up to 125 registers at once
-
Connection Pooling
type ClientPool struct {
clients chan modbus.Client
factory func() (modbus.Client, error)
}
func NewClientPool(size int, factory func() (modbus.Client, error)) *ClientPool {
pool := &ClientPool{
clients: make(chan modbus.Client, size),
factory: factory,
}
// Pre-populate pool
for i := 0; i < size; i++ {
client, _ := factory()
pool.clients <- client
}
return pool
}
func (p *ClientPool) Get() modbus.Client {
return <-p.clients
}
func (p *ClientPool) Put(client modbus.Client) {
p.clients <- client
}- Caching
type CachedDataStore struct {
modbus.DataStore
cache map[string]cacheEntry
cacheLock sync.RWMutex
ttl time.Duration
}
type cacheEntry struct {
data interface{}
timestamp time.Time
}
func (c *CachedDataStore) ReadHoldingRegisters(address modbus.Address, quantity modbus.Quantity) ([]uint16, error) {
key := fmt.Sprintf("hr:%d:%d", address, quantity)
// Check cache
c.cacheLock.RLock()
entry, found := c.cache[key]
c.cacheLock.RUnlock()
if found && time.Since(entry.timestamp) < c.ttl {
return entry.data.([]uint16), nil
}
// Read from underlying store
data, err := c.DataStore.ReadHoldingRegisters(address, quantity)
if err != nil {
return nil, err
}
// Update cache
c.cacheLock.Lock()
c.cache[key] = cacheEntry{data: data, timestamp: time.Now()}
c.cacheLock.Unlock()
return data, nil
}Typical performance metrics on modern hardware:
| Operation | Throughput | Latency |
|---|---|---|
| Read 100 registers (TCP) | ~10,000 req/s | ~0.1ms |
| Write 100 registers (TCP) | ~8,000 req/s | ~0.125ms |
| Read single coil (TCP) | ~15,000 req/s | ~0.067ms |
| Read 100 registers (RTU 115200) | ~50 req/s | ~20ms |
| Read 100 registers (RTU 9600) | ~5 req/s | ~200ms |
// Issue: dial tcp 192.168.1.100:502: connect: connection refused
// Solutions:
// 1. Check if server is running
// 2. Verify IP address and port
// 3. Check firewall settings
// 4. For Linux, check if port needs sudo (ports < 1024)// Issue: operation timeout after 3s
// Solutions:
// 1. Increase timeout
client.SetTimeout(10 * time.Second)
// 2. Check network latency
// 3. Reduce request size
// 4. For serial, check baud rate and cable length// Issue: MODBUS Error [ReadHoldingRegisters]: IllegalDataAddress
// Solutions:
// 1. Verify address is within valid range
// 2. Check if registers are configured on device
// 3. Some devices use 1-based addressing (add 1 to address)
// 4. Check device documentation for memory map// Issue: CRC error in response
// Solutions:
// 1. For serial: Check cable quality and connections
// 2. Reduce baud rate
// 3. Add termination resistors (RS-485)
// 4. Check for electrical interferencetype LoggingTransport struct {
transport.Transport
logger *log.Logger
}
func (lt *LoggingTransport) SendRequest(slaveID byte, req *pdu.Request) (*pdu.Response, error) {
lt.logger.Printf("Request: SlaveID=%d, FC=%02X, Data=%X",
slaveID, req.FunctionCode, req.Data)
resp, err := lt.Transport.SendRequest(slaveID, req)
if err != nil {
lt.logger.Printf("Error: %v", err)
} else {
lt.logger.Printf("Response: FC=%02X, Data=%X",
resp.FunctionCode, resp.Data)
}
return resp, err
}func analyzeProtocol(data []byte) {
fmt.Println("Protocol Analysis:")
fmt.Printf("Raw bytes: % X\n", data)
if len(data) >= 7 {
// Check for MBAP header (TCP)
transID := binary.BigEndian.Uint16(data[0:2])
protoID := binary.BigEndian.Uint16(data[2:4])
length := binary.BigEndian.Uint16(data[4:6])
unitID := data[6]
if protoID == 0 {
fmt.Println("Protocol: MODBUS TCP")
fmt.Printf("Transaction ID: %d\n", transID)
fmt.Printf("Length: %d bytes\n", length)
fmt.Printf("Unit ID: %d\n", unitID)
if len(data) > 7 {
pduData := data[7:]
fmt.Printf("Function Code: 0x%02X\n", pduData[0])
fmt.Printf("PDU Data: % X\n", pduData[1:])
}
}
}
// Check for RTU frame
if len(data) >= 4 {
slaveID := data[0]
funcCode := data[1]
crc := binary.LittleEndian.Uint16(data[len(data)-2:])
calcCRC := calculateCRC(data[:len(data)-2])
fmt.Println("Possible RTU frame:")
fmt.Printf("Slave ID: %d\n", slaveID)
fmt.Printf("Function Code: 0x%02X\n", funcCode)
fmt.Printf("CRC: 0x%04X (calculated: 0x%04X)\n", crc, calcCRC)
if crc == calcCRC {
fmt.Println("CRC: Valid")
} else {
fmt.Println("CRC: Invalid")
}
}
}import (
"net/http"
_ "net/http/pprof"
"runtime/pprof"
)
// Enable profiling endpoint
go func() {
log.Println(http.ListenAndServe("localhost:6060", nil))
}()
// CPU profiling
cpuFile, _ := os.Create("cpu.prof")
pprof.StartCPUProfile(cpuFile)
defer pprof.StopCPUProfile()
// Memory profiling
memFile, _ := os.Create("mem.prof")
defer pprof.WriteHeapProfile(memFile)
// Analyze with: go tool pprof cpu.profModbusGo provides a complete, production-ready MODBUS implementation with:
- Full protocol compliance with MODBUS specification V1.1b3
- Support for all standard function codes
- Multiple transport options (TCP, RTU, ASCII)
- Comprehensive error handling
- Thread-safe operations
- Extensive testing
- Clean, maintainable architecture
The library is suitable for:
- Industrial automation systems
- SCADA applications
- IoT gateways
- PLC communication
- Building automation
- Energy management systems
- Testing and simulation tools
For additional support or contributions, please visit the GitHub repository.